Two drawings in.
Nine comments out.Structural drawing review against the architectural plan, with PDF markup

A structural drawing review for coordination compares the engineer’s drawing with the architectural plan and records discrepancies for the engineer to resolve. ArchX compared the engineer’s general arrangement drawing with the architect’s first-floor plan, caught the wrong revision and marked up the drawing with nine comments showing the two sets of values. It prepared a comment sheet and proposed status C, “not accepted, revise and resubmit,” in 4 minutes 37 seconds.

The run in the video used the England edition of ArchX, with English terms, rules and pounds. For firms in the U.S., ArchX has its own edition with U.S. terms, units and rules.

What goes in.

Two PDF drawings at 1:50: the engineer’s GA at revision P02 and the architect’s plan at P04. One request: check the GA (we expected P03), mark it up with numbered comments, give me a comments sheet and propose a status A, B or C.

What ArchX does.

  1. 01

    Checks the revisions

    The GA is P02, not P03, and it is based on the architect’s P03, while the plan is now at P04.

  2. 02

    Adds up the dimensions

    The north string totals 10,215 mm against 10,115 mm stated: the hall is drawn 2,600 mm wide, ours is 2,500 mm.

  3. 03

    Compares walls, doors and levels

    Wall W1 is 140 mm, ours 215 mm. The hall doorway is 800 mm, ours 900 mm clear. The slab is at +2.700 m, ours at +2.750 m.

  4. 04

    Finds what is missing

    The plant room (mechanical room) doorway is not on the GA, and a 300 × 300 mm duct penetration appears that is not on our plan.

What comes back.

  • The marked-up GA as PDF, three pages, with the comments sheet
  • The comments sheet as Excel, with columns for the engineer’s response
  • A cover note ready to copy

The figures from the run.

4 min 37 s

working time for one request

9

numbered comments

C

proposed status: not accepted, revise and resubmit

What stays with you.

The status is yours to authorize. The review covers coordination, not structural adequacy, and says what two plans cannot show, such as slab details and installed door clearances. It covers P02 only. The drawing received stays unchanged, and nothing is sent.

Where the video comes from.

A recorded run of the ArchX England edition on November 1, 2026 (blind-test task gb-01-ga-review). The project is a test project with a fictitious engineer and differences planted on purpose. The video shows this run, re-staged and sped up.

What the video says.

The video has music and no voice. This is the text that appears on screen, in the order of the video.

  1. Two drawings in. Nine comments out.
  2. The engineer's GA and our ground floor plan
  3. Check the engineer's GA against our ground floor plan rev P04 (we expected P03). Mark it up with numbered comments, our value vs theirs, a comments sheet to send back and a status A, B or C.
  4. Registers the drawings for the check. Their GA against our plan. Read from the printed dimensions, nothing scaled.
  5. Reads the text on the drawing. Wrong revision: P02, not P03. And it is based on our P03, not the current P04.
  6. Checks the dimension strings. The north string does not add up. The hall is drawn 2600 wide; ours is 2500.
  7. Looks at part of the drawing. Wall W1 drawn at 140, ours is 215. It follows: north room 3075 deep, ours 3000.
  8. Looks at part of the drawing. A door too narrow, a slab too low. Plus a plant-room doorway missing and a duct not on our plan.
  9. Issues the marked-up drawing. Nine comments, status C. Proposed: not accepted, revise and resubmit.
  10. Worked for 4 min 37 s
  11. Proposed status C — not accepted; revise and resubmit. Nine comments address revision, dimension, wall, doorway, slab-level and penetration coordination. The supplied GA is P02, not the expected P03.
  12. The engineer's GA, marked up in red. Numbered comments: ours against theirs. Comment 001: the wrong revision. The sheet to send back, status C proposed. Three PDF pages and an Excel sheet.
  13. 5 minutes. From two drawings to nine comments to send. Real run: 4 min 37 s. Every comment: our value against theirs.
  14. Real ArchX run, re-staged and sped up. Fictitious test drawings.

Which program it needs.

The run started from drawings as PDF. Revit, Vectorworks, AutoCAD, Archicad, Allplan and SketchUp all print drawings to PDF, so a practice in any of them gives ArchX the same kind of file. The video itself shows none of these programs.

Explained briefly.

General arrangement drawing (GA)
The engineer’s drawing showing the layout of structural elements. ArchX used the GA to compare wall thicknesses, slab elevations and openings with the architect’s first-floor plan.
Drawing revision
The issue identifier on a drawing. The review found revision P02 where the firm expected P03, and recorded which architect’s revision the engineer had used.

Asked briefly.

What should you check when reviewing structural drawings for coordination?

In this run, ArchX checked the sheet revisions first, then compared dimensions, wall thicknesses, openings and slab elevations. It numbered the comments on the marked-up PDF and listed them on a separate comment sheet.

Does ArchX scale from the drawings?

Not in this run. It read every value from the printed dimensions, and the review says so.

Does it list what agrees?

Yes. After the comments the review lists what matches, from the overall size to the stair void (stair opening).

Does this work if we draw in Revit, Vectorworks or AutoCAD?

Yes. The run started from drawings as PDF. Revit, Vectorworks, AutoCAD, Archicad, Allplan and SketchUp all print drawings to PDF, so a practice in any of them gives ArchX the same kind of file. The video itself shows none of these programs.